Step 2
- Remove the soil above the zone
to be sampled (see Figure 2).
- Take the soil sample from the center of the effective root zone. For
example, if the effective root
depth is 12 inches, the sample
should be taken in the 5- to 8-inch depth range.

Figure 2. Location from which to take undisturbed soil
core.
Step 3
- Use a hammer to tap the cylindrical tube into the soil (Figure 3) so
that the top of the tube is flush with the excavated soil.
- Cut the soil 1/2 inch below the base of the tube with a knife or
trowel.
- Remove the tube and soil without
spilling any of the soil from inside the tube. (The soil should
completely fill the tube).

Figure 3. The core is tapped into the soil to take an undisturbed sample
from the center of the effective root zone.
Step4
- Trim the soil at each end of the tube to the tube length (Figure 4)
so that the soil occupies the exact tube volume.

Figure 4. Trimming the soil core to the exact length of the cylindrical
tube.
Step 5
- Immediately empty the soil from
the tube into a plastic container
(plastic bag) so the soil can be
transported to the weig}ung location without drying. Be sure all of
the soil is transferred from the tube to the plastic container.
Step 6
- Empty all of the soil from the
plastic container to an oven-safe
container and weigh it immediately. This is the wet weight of
the soil plus the container
Step 7
- Place the sample now held in the
oven-safe container into an oven
and dry it for 24 hours at 220 degrees F.
Step 8
- Weigh the dried sample and oven container. This is the dry weight of
the soil plus the container (Wds+c).
Step 9
- Discard the soil and weigh the empty oven container (Wc).
Step 10
- Use the following equation to determine the volumetric water content
(Vw) of the sample:
Vw =
Vw =
The standard English unit for the density of water (DW) is 62.4 pounds per
cubic foot. However, for working with small samples, a more convenient unit
for
DW is 0.578 ounces per cubic inch. An example calculation is given in the
calibration example.
Example: Field Calibration of a Tensiometer
Step 1
- Prepare two tensiometers for field
installation. (Preparation and installation procedures are discussed in
Extension Publication AG 452-2, Measuring Soil-Water for Irrigation
Scheduling: Monitoring Methods and Devices.)
Step 2
- Install each tensiometer at locations in the field that represent
average field conditions. (Tensiometers should be placed in the
row if the field is bedded or a crop is growing).
- Each tensiometer should be installed with the porous tip
centered at one-half the effective root zone depth (typically 5 to 8
inches deep).
Step 3
- Check tensiometer readings immediately following a soaking
rain (1 to 2 inches within 24 hours). They should read near
zero (less than 3 centibars (cb) if their length is 12 inches).
Step 4
- Begin measurements for sandy to
sandy loam soils approximately
24 hours after the rain ends. The
soil should be near field capacity
by this time.
- Record the tensiometer reading.
The tensiometer will read around
5 to 10cb.
Step 5
- Collect a soil sample near each tensiometer at the depth of the
porous tip. Each sample should
be collected, weighed, and dried
according to the procedure outlined in the previous section
("Determining Soil-Water by the Gravimetric Method").
- Take the gravimetric soil sample
about 12 inches from the tensiometer so that the soil around
the tensiometer is not disturbed. Replace unused soil.
Step 6
- Repeat steps four and five at least
twice per day (around midday and late afternoon) until the
tensiometer readings exceed 70 cb. (This sampling frequency is
for calibration during periods of
high evapotranspiration, May to
October. Otherwise, measurements can be made once every 24
hours at any time of day).
- Take samples from an undisturbed area on either side of the
row near the tensiometers (Figure 5). Replace unused soil after
collecting each gravimetric soil sample. At least two samples near
each tensiometer should be undisturbed so that bulk density can be
computed. Tensions above 20 cb are not easily obtained in the field
unless plants are growing or no rainfall occurs for several weeks.

Figure 5. During the calibration process, gravimetric soil samples should
be taken along the row at the same distance from the center of the row as the
tensiometer or electrical resistance block. After collecting each sample,
replace unused soil.
Step 7
- The above measurements will establish the moist range of the
calibration curve. The permanent
wilting point (POOP) water content is difficult to measure in the
field. A gravimetric soil sample can be collected when a growing
crop begins to remain continuously wilted for 24 hours. Otherwise,
a soil sample should be sent to a laboratory so that the PWP water
content can be determined by a laboratory procedure. If the PWP
cannot be determined by one of the laboratory procedures, it may
be estimated as one-half the water content at field capacity for
most soil textures except soils with a clay content greater than
about 35 percent.
Sample Calculations for the Calibration Procedure
Assume that the data in Table 2 were
collected to calibrate a tensiometer as
outlined above. Bulk density was
determined on two undisturbed
cylindrical core samples (3 inches in
diameter by 3 inches in length). The
bulk density can be computed from
the volume of the core and the
average weight of the undisturbed
oven-dry samples.

Volume of core = 3.14(3in.)(3in.)(3in.)/4 = 21.2 in3
Average dry weight of two undisturbed samples:
Bulk density of the soil:
The water content of each sample
can be computed by the equation in
step 10 of the gravimetric method. For
example, the volumetric water content
for sample 2 in Table 2 would be:
Vw of sample 1
Note: Water content for remaining samples is
shown In Table 3.

Several laboratory methods have
been developed to determine soil-water versus tension from both
disturbed and undisturbed core samples.
With the exception of POOP, however,
field-determined calibration curves
are more reliable than laboratory
calibrations. Laboratory methods are
about the only alternative for determining POOP. The cost of laboratory
analysis is about $5 per tension measurement per core sample. Thus the
total cost of laboratory analysis may
approach $50 per core sample to
define the full range of PAW.
Summary
Although most manufacturers provide
calibration curves for soil-water
measuring devices, it is important to
perform field calibrations for this
equipment for each major soil type
that requires irrigation scheduling.
After becoming familiar with the procedures discussed in this publication,
be sure to:
- Check your soil-water measuring
devices for storage damage or deterioration before installing
them in the field.
- Place the devices in representative areas of the field.
- Be sure to calibrate all new
devices.
- Take all measurements with care and accuracy.
- Use the formulas provided in this
publication to perform the calculations necessary to calibrate
your devices.
- Check the performance of your
soil-water measuring equipment, especially tensiometers, weekly.
For further information on calibrating soil-water measuring
devices, contact your county Extension Service office.